IPL EXP PDU4H |
|
Memory |
SDRAM | 512 MB |
Flash | 512 MB |
|
Software |
Configuration software | Global Configurator® Plus and Professional |
Programming software | Global Scripter® |
Control apps | Extron Control, iGVE |
Resource management software | GlobalViewer® Enterprise |
Utilities | Toolbelt, embedded web page |
|
Ethernet |
Network interface controllers (NICs) | 1 |
Connectors | 1 female RJ-45 connector |
Data rate | 10/100Base-T, half/full duplex with autodetect |
Protocols | ARP, DHCP, DNS, HTTP (redirect), HTTPS, ICMP (ping), IEEE 802.1X, NTP, SMTP, SNMP, SSH, TCP/IP, UDP/IP |
Default settings | Link speed and duplex level = autodetected IP address = 192.168.254.250 Subnet mask = 255.255.255.0 Gateway = 0.0.0.0 DHCP = off DNS = 127.0.0.0 |
|
Manual control contact input |
Quantity/type | 4 contact closure inputs for exclusive control of AC power outputs |
Contact closure ports | (2) 3.5 mm captive screw connectors, 3 pole |
Contact closure (input only) | |
Input voltage range | 0 to 5 VDC, clamped at +5.1 V |
Input impedance | 10k ohms |
Threshold low to high | 2.8 VDC |
Threshold high to low | 2.0 VDC |
Pin configuration | Pins 1, 2, 3, 4 = inputs 1, 2, 3, 4; pin G on each connector = Gnd |
|
Relay |
Quantity/type | 1 normally open relay |
Relay control connectors | (1) 3.5 mm captive screw connector, 2 pole |
Relay control contact rating | 24 VDC, 1 A |
|
Switched AC power output |
Connectors | 4 female IEC power receptacles |
Voltage | 120/240 VAC, 50-60 Hz |
Maximum AC load | |
USA/Canada | 12 A at 120 VAC |
International | 10 A at 240 VAC |
Current sense | |
Range | 0 A to 12 A |
Resolution | 100 mA |
Tolerance | ≤6% |
Current sensor aging | <2% |
Surge protection | Single-stage – multiple MOVs |
Peak impulse current (8/20 µs waveform) | • 30,000 A, one time - maximum peak impulse current pulse as defined between line and neutral • 19,500 A, two times within 5 minutes |
Protection mode | • Line to neutral
• Line/neutral to ground |
Response time | <25 nanoseconds |
Surge energy dissipation | 1750 joules (10/1000 µs) |
EMI/RF suppression | None. Input AC is looped and passed to AC output.
|
|
General |
Power supply | Internal Input: 120/240 VAC, 50/60 Hz |
Power consumption | 1.5 watts (with no load at the AC outputs) 2410.5 watts (full load) |
Ambient temperature/humidity | Storage: -40 to +158 °F (-40 to +70 °C) / 10% to 90%, noncondensing Operating: +32 to +122 °F (0 to +50 °C) / 10% to 90%, noncondensing |
Cooling | Convection, no vents |
Thermal dissipation | 5.1 BTU/hr (with no load at the AC outputs) 118.1 BTU/hr (with full load) |
Mounting | |
Rack mount | Yes, with optional 1U rack shelf |
Furniture mount | Yes, with optional bracket kit |
Enclosure type | Metal |
Enclosure dimensions | 1.7" H x 8.7" W x 8.5" D (1U high, half rack wide) (43 mm H x 221 mm W x 216 mm D) (Depth excludes connectors.) |
Product weight | 2.2 lbs (1.0 kg) |
Regulatory compliance | CE, C-Tick, c-UL, FCC Class B, ICES, UL, VCCI Complies with the appropriate requirements of RoHS, WEEE |
Product warranty | 3 years parts and labor |
NOTE | All nominal levels are at ±10%. |
|
NOTE | Specifications are subject to change without notice. |
|
(6192-D5) |