OCS 100

Occupancy Sensors
Key Features
  • Dual technology US - Ultrasonic and PIR - Passive Infrared sensors provide a wide coverage area with excellent detection capabilities
  • Smart, adaptive software automatically and continuously adjusts timer settings and sensitivity, providing a lifetime of maintenance-free operation
  • Non-volatile memory for sensor settings
  • Infrared sensitivity knob helps minimize false triggers
  • Adjustable timer conserves energy
  • Status LED's flash when occupancy is detected
The Extron OCS 100
Model Version Description Part #
 OCS 100C Ceiling Mount 60-1664-01
 OCS 100W Wall Mount 60-1665-01

The Extron OCS 100C and OCS 100W are ceiling and wall-mount occupancy sensors that provide exceptional coverage using ultrasonic and passive infrared detection technologies. Integrated smart, adaptive software automatically and continuously monitors the environment and adjusts timer settings and sensitivity, providing a lifetime of dependable detection and maintenance-free operation. These occupancy sensors are tested for use, worldwide, and are ideal for any business application where various occupancy-dependent automation scenarios or conscientious energy management are needed.

Features

  • Dual technology US - Ultrasonic and PIR - Passive Infrared sensors provide a wide coverage area with excellent detection capabilities
  • Smart, adaptive software automatically and continuously adjusts timer settings and sensitivity, providing a lifetime of maintenance-free operation
  • Non-volatile memory for sensor settings
  • Infrared sensitivity knob helps minimize false triggers
  • Adjustable timer conserves energy
  • Status LED's flash when occupancy is detected
  • Relay and photocell control
  • Coverage area:
    - OCS 100C - 2,000 square feet
    - OCS 100W - 1,600 square feet
  • UL and cUL listed
  • California Title 24 compliant
  • DIP switches for fine tuning device settings
  • Includes Extron PC 1224 – Adapter features a 24V output that can be supplied via a 12V input or via a 5V USB type-C input from compatible TouchLink Pro touchpanels or TouchLink scheduling panels
COMPATIBLE PRODUCTS
  IPCP Pro 355DR IP Link Pro Control Processor - DIN Rail
  IPCP Pro 360 IP Link Pro Control Processor
  IPCP Pro 550 IP Link Pro Control Processor
  MLC Plus 84 D MediaLink Plus Controller - Decorator-Style Wallplate
  MLC Plus 84 EU MediaLink Plus Controller - EU Wallplate
  MLC Plus 84 MK MediaLink Plus Controller - MK Wallplate
  MLC Plus 50 MediaLink Plus Controller
  MLC Plus 100 MediaLink Plus Controller
  MLC Plus 100 AAP MediaLink Plus Controller with AAP Opening
  MLC Plus 200 MediaLink Plus Controller
  MLC Plus 200 AAP MediaLink Plus Controller with AAP Opening
  MLC 226 IP Enhanced MediaLink Controller with Ethernet Control
  MLC 62 RS D MediaLink Controller with RS-232 Control - Decorator-Style Wallplate
  MLC 62 RS CC MediaLink Controller for Cable Cubby Cable Access Enclosures
  MLC 62 RS EU MediaLink Controller for EU Junction Boxes
  MLC 62 RS MK MediaLink Controller for MK Junction Boxes
SIMILAR PRODUCTS
  ECM S10 Partition Sensor Set
  KNX 100G KNX IP Interface

Specifications

OCS 100 Occupancy Sensors
OCS 100C
   Square feet coverage area 2000 square feet
    
    NOTE     These coverage dimensions are achieved when the OCS 100C is installed 10 ft (3.04 m) above the coverage area.
OCS 100W
   Square feet coverage area 1600 square feet
    
Sensor
   InteliDAPT® technology Auto reset from test setting
Self-adjusting timer
Self-adjusting passive infrared thresholds
Automatic false-on and false-off correction
   LED lamp Red - infrared motion
Green - ultrasonic detection
   Timer timeout 
      OCS 100C Automatic mode: 8 to 42 minutes (self-adjusts based on occupancy)
Manual mode: 8 to 42 minutes
Test mode: 8 seconds
      OCS 100W Automatic mode: 4 to 30 minutes (self-adjusts based on occupancy)
Manual mode: 4, 8, 15 and 30 minutes
Test mode: 8 seconds
   Ultrasonic (US) 
      OCS 100C 4 sensors - 32 kHz output
      OCS 100W 2 sensors - 32 kHz output
   Passive infrared (PIR) 
      OCS 100C Dual-element pyrometer and 12-element cylindrical segmented Fresnel lens, integral filter excludes excess PIR energy from sunlight
      OCS 100W Dual-element pyrometer and 12-element cylindrical rugged lens
Relay
   Relay 1 Normally Open and Closed contact, single pole, double throw 500 mA rated at 24 VDC, three-wire isolated relay
Photocell
   Photocell Adjustable natural-light override ranges from 1 to 100 foot-candles (10 to 1000 Lux)
Adaptive functions
   Learning 4 weeks for response error conditions, air current adaption and timer optimization
   Post-learning occupancy periods 24-hour circadian occupancy periods learned
   Adjustments in post-learning period Generally occupied periods
Generally unoccupied periods
Digital output
   Quantity/type 2 digital outputs
   Connectors Blue wire = Occupancy only
Gray wire = Occupancy + Photocell
   Output voltage range 0 - 24 VDC
Active high logic control signal with short-circuit protection, open collector when unoccupied
General
   Sensor power input requirements 20-24 VDC, 33 mA nominal
    NOTE     If power is supplied by an optional 12 VDC power supply, then use the included PC 1224 to convert 12 VDC to 24VDC.
   PC 1224 power requirements Input: 12 VDC, 1.5 A max
Output: 12 VDC, 1.25 A max
              24 VDC, 75 mA max
   Wiring Color coded, pre-stripped leads - 6" (15 am) in total length
   Ambient temperature/humidity Operation: +32 to +104 °F (0 to +40 °C) / 0% to 95 %, noncondensing
For indoor use only
   Cooling Convection, no vents
   Mounting Mounting base provided
Recommended mounting height: 8 feet with a max mounting height of 12 feet
   Enclosure type  Plastic
   Enclosure dimensions 
      OCS 100C 4.50" W x 1.40" D
(114 mm W x 36 mm D)
       
      OCS 100W 2.80" W x 5.50" L  x 2.10" D
(71 mm W x 140 mm x 53 mm D)
       
      PC 1224 1.00" W x 1.00" L x 0.50" D
(25 mm W x 25 mm L x 13 mm D)
   Product weight  0.1 lb (<0.1 kg)
   Color Off-white
   Regulatory compliance CE, c-UL, UL, FCC Class A, KC
Complies with appropriate requirements of RoHS, WEEE, and California Title 24
   Product warranty 3 years parts and labor
   Everlast power supply warranty 7 years parts and labor
    NOTE     Specifications are subject to change without notice.
(5611-D6)
Shipping Dimensions and Weights
    Part # Height Width Depth Weight
    60-1664-01 2.5" (6.4 cm) 6.75" (17.1 cm) 5.25" (13.3 cm) 0.55 lbs (0.25 kg)
    60-1665-01 2.75" (7.0 cm) 9.75" (24.8 cm) 4.75" (12.1 cm) 0.65 lbs (0.29 kg)

Diagram

OCS 100W Diagram

Room Scheduling Diagram

Occupancy Sensor wiring with TouchLink Scheduling Touchpanels Diagram

Panel Drawing

OCS 100 Panel Drawing